IEC60092 Offshore & Marine Cables | |||
MariTox Marine Flame Retardant Medium Voltage Cables | MariTox Marine Flame Retardant Power & Control Cables | MariFlex Marine Fire Resistant Power & Control Cables | other |
Power Distribution Cables
5000V three conductors Type E, X distribution cables
Construction
Conductor: Stranded copper conductor tin or alloy coated where necessary for the application , conductor per
ASTM or IEC 60228.
Separator tape: optional
Insulation: Ethylene propylene rubber(EPR), or cross-linked polyethylene(XLPE) according to IEEE 1580 2010
Type E, X,Type T, T/N, S, P, LSX and LSE as option.
Shielding: optional
Jacket:Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or
TPO jacket as option (optional for Type P with HD thicknesses).
Armor: optional and shall be nonmagnetic
Sheath:Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or
TPO sheath as option (optional except for tinned copper braid armoured cables).
Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO
jacket/sheath.
Table B.6—Typical dimensions and weights; three-conductor 5000 V; Type E and X distribution cables
AWG /kcmil |
Unarmored | Armored | Armored and sheathed | |||
---|---|---|---|---|---|---|
Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | Nom. dia. (in) | Approx. weight (lb/1000 ft) | |
8 | 1.14 | 783 | 1.2 | 839 | 1.37 | 1050 |
6 | 1.21 | 934 | 1.27 | 999 | 1.44 | 1221 |
4 | 1.33 | 1163 | 1.39 | 1234 | 1.56 | 1476 |
2 | 1.46 | 1541 | 1.52 | 1619 | 1.75 | 1981 |
1 | 1.56 | 1760 | 1.62 | 1843 | 1.85 | 2227 |
1/0 | 1.63 | 2035 | 1.69 | 2121 | 1.92 | 2521 |
2/0 | 1.79 | 2498 | 1.85 | 2592 | 2.08 | 3028 |
3/0 | 1.91 | 2946 | 1.97 | 3049 | 2.2 | 3511 |
4/0 | 2.03 | 3476 | 2.09 | 3584 | 2.32 | 4073 |
250 kcmil | 2.13 | 4006 | 2.19 | 4120 | 2.42 | 4631 |
300 kcmil | 2.25 | 4611 | 2.31 | 4725 | 2.54 | 5263 |
350 kcmil | 2.36 | 5210 | 2.42 | 5324 | 2.65 | 5886 |
400 kcmil | 2.46 | 5767 | 2.52 | 5881 | 2.82 | 6653 |
500 kcmil | 2.69 | 7008 | 2.75 | 7122 | 3.04 | 7932 |
600 kcmil | 2.92 | 8331 | 2.98 | 8445 | 3.28 | 9350 |
750 kcmil | 3.15 | 9068 | 3.21 | 9182 | 3.51 | 10 153 |
Dimensions are based on the use of Class B conductors. Weights of armored constructions are based on aluminum braid armor. It is recommended that the user/specifier contact the manufacturer for manufacturer specific values.